Product Overview
The VENEMA VCP-FFCP Series is engineered to control and monitor fire pump systems in compliance with international safety standards. These panels manage main, jockey, and standby pumps to ensure continuous water delivery in emergencies. Built with reliable components and protective logic, the FFCP Series provides automatic operation, alarm indication, and safety interlocks essential for firefighting systems.
Construction & Design Features
- Rigid powder-coated metal enclosure (IP54 / IP65)
- Separate circuits for main, jockey, and standby pumps
- Auto, manual, and test operation modes
- Indicator lamps for pump status and system faults
- Alarm buzzer with acknowledge/reset function
- Phase failure, under-voltage, and overload protection
- Pressure or flow switch interface for automatic start
Applications
- Building and commercial fire protection systems
- Industrial facilities and warehouse hydrant networks
- Irrigation or water supply pumping stations with fire duty
- Any installation requiring reliable pump start control in emergency conditions
Standar Features
Optional Features
- Soft starter or VFD for main pump motor
- Auto change-over between main and standby pumps
- Integration with re alarm or BMS systems
- Remote monitoring or SCADA interface
- Stainless-steel or outdoor-rated enclosures
- Custom mimic diagram or labeling
Operation Principle
The system monitors water pressure via a pressure or flow switch.
When pressure falls below the threshold, the jockey pump starts automatically. If pressure continues to drop, the main pump is activated to maintain flow. In the event of failure, the standby pump automatically engages. Once normal pressure is restored, the pumps stop sequentially.
Operating Conditions
- Ambient temperature: −5 °C to +40 °C
- Relative humidity: ≤ 80 % (at 20 °C)
- Installation altitude: ≤ 1000 m above sea level
- Environment: Clean, dry, and ventilated indoor areas
Power Range Specifications
- Main Pump Motor Ratings: 7.5 kW – 250 kW
- Jockey Pump Motor Ratings: 0.75 kW – 7.5 kW
- Standby Pump Motor Ratings: up to 250 kW
- Control Voltage: 220 V AC / 50 Hz or 24 V DC (optional)
- Starter Types:
- DOL (up to 15 kW)
- Star-Delta (15–90 kW)
- Soft Starter / VFD (> 90 kW)
- Main Circuit Breaker Ratings: 63 A – 800 A
- Customization : Higher ratings and multi-pump configurations available on request
Example Application